The national grid and transformer calculations

Practise 15 exam-style questions on The national grid and transformer calculations for Edexcel GCSE Combined Science (Foundation Physics Paper 2). Write your answer as you would in the exam and get it marked in seconds against the mark scheme, point by point, with the Study Helper on hand if you get stuck.

  • 15 questions
  • 1–6 marks each
  • Instant marking
  • No sign-up needed
15 questions, marked as you go

Sample questions with model answers

Here are 4 of the questions in this topic, each with a model answer, an explanation of why it earns the marks and the mark scheme an examiner would use.

Question 1

1 mark

In the national grid, where are step-down transformers used?

Choose your answer.

  • A between the generator and the transmission cables
  • B inside the generators at power stations
  • C between the transmission cables and the homes they supply
  • D only inside household appliances

Model answer

C - between the transmission cables and the homes they supply

Explanation

At the power station a step-up transformer increases the potential difference before the electricity enters the transmission cables. Near the places where it is used, step-down transformers reduce the potential difference in stages, down to 230 V for homes. Remember: step up at the start, step down at the end.

Mark scheme
  1. 1 mark

    C / between the transmission cables and the homes they supply

    The only correct answer is C: step-down transformers reduce the very high potential difference of the transmission cables to lower values, and finally to 230 V for homes, which is safer. A is not correct because the transformer between the generator and the transmission cables is a step-up transformer; B is not correct because a generator produces the electricity and does not contain the grid's transformers; D is not correct because the national grid's step-down transformers are in substations and near homes, not in appliances. Accept the letter or the option. If more than one option is given, do not award the mark.

Question 2

2 marks

In the early 1900s, many British towns had their own small power station. Electricity was sent to nearby homes along short cables, at a low potential difference.

Today's national grid sends electricity hundreds of kilometres from power stations to homes, at very high potential differences.

Suggest why the small town power stations could use a low potential difference, but the national grid cannot.

Model answer

The town cables were short, so even though the low potential difference meant a large current, only a little energy was wasted heating them. The national grid's cables are hundreds of kilometres long, so a large current would waste a lot of energy heating them. A very high potential difference gives a small current, which keeps this wasted energy small.

Explanation

The energy wasted in cables comes from the heating effect of the current, and long cables waste more than short ones. For a short distance a large current at a low potential difference is acceptable; for hundreds of kilometres the current must be made small, which needs a very high potential difference.

Mark scheme
  1. 1 mark

    the town cables were short (the homes were close to the power station), so the energy wasted heating them was small, even with a large current

    accept 'short cables waste less energy by heating' / 'there was not far for the electricity to travel, so little energy was lost'.

  2. 1 mark

    the national grid's cables are very long, so a low potential difference (large current) would waste a lot of energy heating them / a high potential difference gives a small current, which reduces the heating of the long cables

    accept 'over long distances a large current would make the cables very hot'. Do not accept 'the electricity would not reach the homes' with no reference to energy wasted or heating.

Question 3

3 marks

A power station supplies 1200 MW of electrical power to the transmission cables at a potential difference of 400 kV.

Calculate the current in the transmission cables.

Model answer

electrical power = current × potential difference
current = power ÷ potential difference
current = 1 200 000 000 ÷ 400 000 = 3000 A

Explanation

Recall electrical power = current × potential difference and rearrange it to current = power ÷ potential difference. Convert MW to W (× 1 000 000) and kV to V (× 1000) first. Even at 400 kV the current is thousands of amps, which shows why a low potential difference would need an impossibly large current.

Mark scheme
  1. 1 mark

    conversions: 1200 MW = 1 200 000 000 W and 400 kV = 400 000 V; or a correct final answer of 3000 A / 3 kA with no working

    An answer of 3000 A or 3 kA with no working scores 3 marks. Working in MW and kV is accepted if the answer is given as 3 kA (1200 ÷ 400 = 3 kA scores 3 marks). An answer of 3 (A), from not converting MW and kV (power-of-ten error), scores 2 marks. 1200 × 400 = 480 000 or 400 ÷ 1200 = 0.33 (wrong rearrangement) scores 0.

  2. 1 mark

    rearrangement and substitution of power = current × potential difference: (current =) 1 200 000 000 ÷ 400 000; or a correct final answer of 3000 A / 3 kA with no working

    accept 1 200 000 000 = 400 000 × current. accept 1200 ÷ 400 for this mark.

  3. 1 mark

    evaluation: 3000 (A)

    accept 3 kA. Ignore units.

Question 4

4 marks

A data centre uses electrical power at a rate of 6.6 MW. It is supplied by underground cables at a potential difference of 33 000 V, and its own step-down transformers reduce this to 400 V for its equipment.

Use the equation
electrical power = current × potential difference

Calculate the current needed to supply 6.6 MW at 400 V, and the current needed to supply 6.6 MW at 33 000 V. Use your answers to explain why the data centre is supplied at 33 000 V and not at 400 V.

Model answer

current = power ÷ potential difference
At 400 V: current = 6 600 000 ÷ 400 = 16 500 A
At 33 000 V: current = 6 600 000 ÷ 33 000 = 200 A

At 33 000 V the current in the supply cables is more than 80 times smaller. A smaller current heats the cables much less, so much less energy is wasted (and thinner cables can be used). The data centre's own step-down transformers then reduce the potential difference to the 400 V that its equipment needs.

Explanation

Rearrange power = current × potential difference to current = power ÷ potential difference, and convert 6.6 MW to 6 600 000 W first. A data centre needs so much power that supplying it at 400 V would need a huge current, which would heat the cables; this is the same reason the national grid uses high potential differences. Do not say the higher potential difference is safer: it is the smaller current that matters.

Mark scheme
  1. 1 mark

    current at 400 V: 6 600 000 ÷ 400 = 16 500 (A); or a correct final answer of 16 500 A with no working

    An answer of 16 500 A and 200 A with no working scores marking points 1 and 2. If 6.6 MW is not converted to W (0.0165 and 0.0002), award 1 mark in total for marking points 1 and 2.

  2. 1 mark

    current at 33 000 V: 6 600 000 ÷ 33 000 = 200 (A)

    Ignore units.

  3. 1 mark

    at the higher potential difference the current is much smaller (more than eighty times smaller)

    accept a correct comparison of the two calculated currents, including ecf from wrong values.

  4. 1 mark

    a smaller current wastes much less energy heating the supply cables / the supply is more efficient

    accept 'a current of 16 500 A would make the cables very hot' / 'thinner, cheaper cables can be used'. Do not accept '33 000 V is safer' (it is more dangerous).

Ready to try the rest? Every answer you write is marked against the mark scheme, so you can see exactly where the marks are.