The national grid and transformers

Practise 19 exam-style questions on The national grid and transformers for OCR GCSE Physics (Paper 4). Write your answer as you would in the exam and get it marked in seconds against the mark scheme, point by point, with the Study Helper on hand if you get stuck.

  • 19 questions
  • 1–6 marks each
  • Instant marking
  • No sign-up needed
19 questions, marked as you go

Sample questions with model answers

Here are 4 of the questions in this topic, each with a model answer, an explanation of why it earns the marks and the mark scheme an examiner would use.

Question 1

1 mark

In a transformer that is 100% efficient, the potential difference across the secondary coil is one-fifth of the potential difference across the primary coil.

Use the equation: potential difference across primary coil × current in primary coil = potential difference across secondary coil × current in secondary coil

Which statement about the current in the secondary coil is correct?

Choose your answer.

  • A It is one twenty-fifth of the current in the primary coil.
  • B It is one-fifth of the current in the primary coil.
  • C It is five times the current in the primary coil.
  • D It is twenty-five times the current in the primary coil.

Model answer

C

Explanation

Write Vs = Vp ÷ 5 in the equation: Vp × Ip = (Vp ÷ 5) × Is, so Is = 5 × Ip. This is a step-down transformer: it decreases the p.d. and increases the current by the same factor, so the power stays the same. Squaring the factor is a common slip, because the power wasted in cables depends on the current squared.

Mark scheme
  1. 1 mark

    C / It is five times the current in the primary coil.

    The only correct answer is C: the power (p.d. × current) is the same on both sides of the equation, so if the p.d. across the secondary coil is five times smaller, the current in it must be five times larger. A is not correct because the current increases when the p.d. decreases, and the factor is not squared. B is not correct because the current changes in the opposite way to the p.d. (the current decreases only in a step-up transformer). D is not correct because the current is not squared in this equation (twenty-five confuses it with the power wasted in a cable, which depends on the current squared). ALLOW the letter or the option. If more than one option is given, do not award the mark.

Question 2

2 marks

A transmission line in the national grid works at a potential difference of 400 kV. The current in the line is 1150 A.

A house is supplied at 230 V. When several appliances are switched on, the current in the cable to the house is 20 A.

Estimate how many houses, each taking a current of 20 A at 230 V, the transmission line could supply at the same time. Ignore any energy wasted in the national grid.

Model answer

Power carried by the line = p.d. × current = 400 000 × 1150 = 460 000 000 W
Power to one house = 230 × 20 = 4600 W
Number of houses = 460 000 000 ÷ 4600 = 100 000

Explanation

Compare powers, not currents, using power = p.d. × current. The line's current is only 57.5 times a house's current, but its p.d. is about 1700 times larger, so it carries 100 000 times the power. This is why the national grid transmits at a very high p.d.: a large power is transferred with a small current, which wastes less energy heating the cables. Comparing the currents alone gives about 58 houses, far too few.

Mark scheme
  1. 1 mark

    recall power = potential difference × current: power carried by the line = 400 000 × 1150 = 460 000 000 W (460 MW) and power to one house = 230 × 20 = 4600 W; or a correct final answer of 100 000 houses with no working

    An answer of 100 000 with no working scores 2 marks. ALLOW the working in kV and kW: 400 × 1150 = 460 000 kW and 0.23 × 20 = 4.6 kW. ALLOW the ratio method: (400 000 ÷ 230) × (1150 ÷ 20). 57.5 or 58 (1150 ÷ 20, comparing the currents only) scores 0. 1739 (400 000 ÷ 230, comparing the p.d.s only) scores 0.

  2. 1 mark

    (number of houses = 460 000 000 ÷ 4600 =) 100 000

    ALLOW 1.0 × 10⁵ (typed as 1E5 or 1.0E5). ALLOW ECF from a wrong power shown in the working.

Question 3

3 marks

The list gives the potential differences across the coils of three transformers, P, Q and R, in the national grid.

• transformer P: primary coil 400 kV, secondary coil 132 kV
• transformer Q: primary coil 25 kV, secondary coil 400 kV
• transformer R: primary coil 11 kV, secondary coil 230 V

State whether each transformer is a step-up or a step-down transformer. Give the letter of the transformer that is used at a power station, and explain your answer. Suggest where transformer R is used.

Model answer

Q is a step-up transformer; P and R are step-down transformers.

Q is used at a power station: it increases the p.d. from the 25 kV produced by the generators to the 400 kV of the transmission lines.

R is used in the local area, for example at a small substation in a street near homes, because it reduces the p.d. to 230 V for the homes' supply.

Explanation

A step-up transformer has a greater p.d. across its secondary coil than across its primary coil; a step-down transformer has a smaller one. The national grid steps the p.d. up at power stations, transmits at a very high p.d., then steps it down in several stages, as here, in each locality for domestic use. A common error is to think that the transformer at the power station steps the p.d. down.

Mark scheme
  1. 1 mark

    Q is a step-up transformer; P and R are step-down transformers

    All three are needed for the mark. ALLOW Q increases the p.d. and P and R decrease it.

  2. 1 mark

    Q (is used at a power station), because it increases the p.d. from the p.d. produced by the generators (25 kV) to the very high p.d. of the transmission lines (400 kV)

    The letter Q and a reason are both needed. ALLOW because power stations use step-up transformers so that the power is transmitted at a high p.d. DO NOT ALLOW P or R.

  3. 1 mark

    R is used in the local area near homes / at a small (street) substation near homes, to reduce the p.d. to 230 V for the domestic supply

    ALLOW on a pole or in a substation in the street / in the town / in the village. IGNORE 'at a substation' on its own (P is also at a substation). DO NOT ALLOW at the power station / inside the home.

Question 4

4 marks

A heating mat keeps trays of seedlings warm in a greenhouse. For safety, it works at a low potential difference. The heating mat has a resistance of 12 Ω, and it must have a power of 48 W.

The mat is supplied from the 230 V mains through a transformer. The primary coil of the transformer has 690 turns.

For a transformer:
potential difference across primary coil ÷ potential difference across secondary coil = number of turns in primary coil ÷ number of turns in secondary coil

Calculate the number of turns needed on the secondary coil.

Model answer

power = (current)² × resistance, so (current)² = 48 ÷ 12 = 4.0 and current = 2.0 A
p.d. across the mat = current × resistance = 2.0 × 12 = 24 V
230 ÷ 24 = 690 ÷ number of turns in secondary coil
number of turns in secondary coil = 690 × 24 ÷ 230 = 72 turns

Explanation

The turns ratio must match the ratio of the p.d.s, so first find the p.d. that the mat needs. Use power = (current)² × resistance to find the current (2.0 A), then potential difference = current × resistance (24 V): both equations must be recalled. A step-down transformer that gives 24 V from 230 V needs about a tenth as many turns on its secondary coil as on its primary coil. Common errors are dividing the power by the resistance to get the current, and using the turns-ratio equation the wrong way up.

Mark scheme
  1. 1 mark

    recall power = (current)² × resistance: current = √(48 ÷ 12) = 2.0 (A); or a correct final answer of 72 turns with no working

    An answer of 72 turns with no working scores 4 marks. ALLOW other correct routes to the p.d. across the mat, for example (p.d.)² = power × resistance = 48 × 12 = 576, so the p.d. is 24 V (marking points 1 and 2). ALLOW 3 marks (marking points 2, 3 and 4, by ECF) for 144 turns when the current is wrongly calculated as 48 ÷ 12 = 4.0 A and then used to give a p.d. of 4.0 × 12 = 48 V. ALLOW 2 marks (marking points 3 and 4, by ECF) for 144 turns when the power (48) is used as the p.d.

  2. 1 mark

    recall potential difference = current × resistance: p.d. across the mat = 2.0 × 12 = 24 (V); or a correct final answer of 72 turns with no working

    ALLOW power = potential difference × current: p.d. = 48 ÷ 2.0 = 24 V. ALLOW ECF from an incorrect current.

  3. 1 mark

    substitution into the turns-ratio equation: 230 ÷ 24 = 690 ÷ number of turns in secondary coil / number of turns in secondary coil = 690 × 24 ÷ 230; or a correct final answer of 72 turns with no working

    ALLOW ECF from an incorrect p.d. across the mat. DO NOT ALLOW 690 × 230 ÷ 24 (about 6600 turns: the equation used the wrong way up) for this mark.

  4. 1 mark

    evaluation: 72 (turns)

    ALLOW ECF from their p.d. across the mat shown in the working.

Ready to try the rest? Every answer you write is marked against the mark scheme, so you can see exactly where the marks are.

Study Helper Hints first, answers after you try

Stuck on this one? Ask for a hint and I’ll point you in the right direction, without giving the answer away. Once you’ve checked your answer, I’ll show you how the marks are awarded.