The national grid and transformer calculations

Practise 15 exam-style questions on The national grid and transformer calculations for Edexcel GCSE Combined Science (Physics Paper 2). Write your answer as you would in the exam and get it marked in seconds against the mark scheme, point by point, with the Study Helper on hand if you get stuck.

  • 15 questions
  • 1–6 marks each
  • Instant marking
  • No sign-up needed
15 questions, marked as you go

Sample questions with model answers

Here are 4 of the questions in this topic, each with a model answer, an explanation of why it earns the marks and the mark scheme an examiner would use.

Question 1

1 mark

A transformer is used between the generator at a power station and the transmission cables of the national grid.

Which of these describes this transformer and its effect on the current?

Choose your answer.

  • A step-up, current decreases
  • B step-up, current increases
  • C step-down, current decreases
  • D step-down, current increases

Model answer

A - step-up, current decreases.

Explanation

At the power station a step-up transformer increases the p.d. Because a transformer does not increase the power, Vp × Ip = Vs × Is means the current falls by the same factor as the p.d. rises. Option B is the common error: a transformer cannot increase both the p.d. and the current.

Mark scheme
  1. 1 mark

    A / step-up, current decreases (1)

    The only correct answer is A: a step-up transformer increases the potential difference for transmission; the power stays (almost) the same, so the current decreases (Vp × Ip = Vs × Is). B is not correct because if the p.d. increases at the same power, the current must decrease. C is not correct because a step-down transformer decreases the p.d., and the current would then increase, not decrease. D is not correct because a step-down transformer here would increase the current in the transmission cables and waste more energy; step-down transformers are used near the consumers. Accept the letter or the option. If more than one option is given, do not award the mark.

Question 2

2 marks

A student says: 'The step-up transformer at a power station increases the power sent along the transmission cables, because it increases the voltage.'

Explain why the student is wrong.

Model answer

A transformer cannot give out more power than it takes in, because energy cannot be created. For a 100% efficient transformer Vp × Ip = Vs × Is, so when the step-up transformer increases the potential difference, the current decreases by the same factor and the power (V × I) stays the same. In a real transformer the power out is even slightly less than the power in.

Explanation

Electrical power is current × potential difference, and a transformer only changes how the power is shared between the two: it raises the p.d. and lowers the current, or the reverse. The equation Vp × Ip = Vs × Is is a statement that the power is the same on both sides of an ideal transformer. Thinking that a transformer increases energy or power is a common misconception.

Mark scheme
  1. 1 mark

    a transformer cannot increase the power / the power output cannot be greater than the power input (because energy is conserved) (1)

    An explanation linking the two points. Accept 'for a 100% efficient transformer the power in equals the power out (Vp × Ip = Vs × Is)' or 'in a real transformer the power out is slightly less than the power in'.

  2. 1 mark

    as the p.d. increases, the current decreases (by the same factor), so (V × I) the power stays the same (1)

    Accept 'the voltage goes up but the current goes down'. Do not accept 'the current goes up as well'.

Question 3

3 marks

At a power station, the generator supplies a current of 18 000 A at 22 kV to a step-up transformer. The transformer increases the potential difference to 400 kV for the transmission cables.

Calculate the current in the secondary coil. Assume that the transformer is 100% efficient.

Use the equation
Vp × Ip = Vs × Is

Model answer

Vp × Ip = Vs × Is
22 000 × 18 000 = 400 000 × Is
Is = (22 000 × 18 000) ÷ 400 000
Is = 990 A

Explanation

For a 100% efficient transformer the power in equals the power out, so when the p.d. is increased about 18 times (22 kV to 400 kV) the current falls by the same factor, from 18 000 A to 990 A. The p.d.s can be in kV or in V, as long as both are in the same unit. A current larger than 18 000 A would show that the rearrangement is upside down.

Mark scheme
  1. 1 mark

    substitution: 22 000 × 18 000 = 400 000 × Is (1)

    An answer of 990 (A) with no working scores 3 marks. Allow the p.d.s in kV throughout (22 × 18 000 = 400 × Is).

  2. 1 mark

    rearrangement: Is = 22 000 × 18 000 ÷ 400 000 (1)

    A wrong rearrangement, e.g. 400 000 × 18 000 ÷ 22 000 = 327 000 A, scores only the substitution mark if the substitution is seen.

  3. 1 mark

    evaluation: 990 (A) (1)

    Accept 0.99 kA. An answer with a power of ten error (e.g. 99 A or 9900 A) scores 2 marks.

Question 4

5 marks

A town is supplied with electricity through cables from a substation. At the substation, a transformer reduces the potential difference from 132 kV to 33 kV. The current in the transformer's primary coil is 250 A. Assume that the transformer is 100% efficient.

The cables from the transformer to the town have a total resistance of 0.80 Ω.

Calculate the percentage of the power supplied to the transformer that is wasted heating these cables.

Use the equation
Vp × Ip = Vs × Is

Model answer

Is = (Vp × Ip) ÷ Vs = (132 000 × 250) ÷ 33 000 = 1000 A
Power wasted in the cables = I² × R = 1000² × 0.80 = 800 000 W
Power supplied = Vp × Ip = 132 000 × 250 = 33 000 000 W
Percentage wasted = (800 000 ÷ 33 000 000) × 100 = 2.4%

Explanation

First find the current in the cables from the transformer equation, then use P = I² × R for the heating of the cables, which needs the current and the cables' resistance. The power supplied is Vp × Ip (or Vs × Is, which is the same for a 100% efficient transformer). A common error is to use 33 kV in P = V² ÷ R: 33 kV is the p.d. supplied to the cables and the town together, not the p.d. across the cables themselves (which is only I × R = 800 V).

Mark scheme
  1. 1 mark

    (substitution and rearrangement) Is = 132 000 × 250 ÷ 33 000 (1)

    Award full marks for the correct answer without working. Allow the p.d.s in kV (132 × 250 ÷ 33).

  2. 1 mark

    (evaluation) Is = 1000 (A) (1)

  3. 1 mark

    (power wasted = I² × R =) 1000² × 0.80 = 800 000 (W) (1)

    Allow ecf from the student's value of Is. Using P = V² ÷ R or P = I × V with the 33 kV p.d. for the power wasted is a wrong method (33 kV is not the p.d. across the cables): it does not score this mark or the final mark.

  4. 1 mark

    (power supplied = Vp × Ip =) 132 000 × 250 = 33 000 000 (W) (1)

    Accept Vs × Is = 33 000 × 1000 (the same power, because the transformer is 100% efficient). Accept 33 MW.

  5. 1 mark

    (percentage = 800 000 ÷ 33 000 000 × 100 =) 2.4 (%) (1)

    Accept values that round to 2.4, e.g. 2.42. Allow ecf from the student's power wasted and power supplied, provided the power wasted was found with I² × R. An answer of 2400 (%) or 0.0024 (%) (power of ten error, e.g. from mixing W and kW) scores 4 marks. A fraction of 0.024 not converted to a percentage scores 4 marks.

Ready to try the rest? Every answer you write is marked against the mark scheme, so you can see exactly where the marks are.

Study Helper Hints first, answers after you try

Stuck on this one? Ask for a hint and I’ll point you in the right direction, without giving the answer away. Once you’ve checked your answer, I’ll show you how the marks are awarded.